I'm doing a project on driving a solenoid valve in BOSCH. The input is a
0-10V sine wave (Which is actually an output from a 
D/A converter) and 
it is to be converted to a PWM signal of 300Hz with 0-100% range 
dutycycle. This duty cycle is to be used to 
inject current to drive a 
solenoid valve. For 100% dutycycle, the current should be ideally 1.4A 
to close the valve completely.
Would
using a micro controller give a more accurate PWM signal? 
That wasn't clear from what you wrote.
-You can use a 
simple voltage source. The voltage should be set to U= R . I.
-Switching the voltage on/off with a PWM signal: use the output of
your circuit to drive a mosfet.
Fig 8: 8. Power MOSFET PWM Motor Driver
What you are trying to do is to convert a 0 -
>100% PWM into a 0 ->
1.4A current source. Why?, why not convert your 0 -> 10V AC V into a
0 -> 1.4A current source. 
Or for a 1V ac input, are you are applying
your 300Hz based PWM directly to the solenoid, so for 1V (10%), a pulse
of 1.4A of 
.33mS length is applied every 3.3 mS?
If its just the 0 -> 10 V into a 0 ->1.4A, then build a 
precision rectifier 
as per inventor(y)'s suggestion, then use an op-amp 
with a power transistor using the solenoid as its collector load, and a 
low 
value resistor (1 ohm) in the emitter circuit. So now you have a 
monitoring point for the solenoids current. At 1.4A out, there will 
be 
1.4V dropped across this resistor. So connect your feed back resistor 
from this point to the - input of the amp with another 
resistor to earth
also from the - input. 