Mag Meter
I spoke with Siemens today about their Magmeters they want us to use on our equipment.
He stated flat out that they care not at all about flow runs or pipe and fittings before or after their flow meter.
The 2" model I looked at was flanged on either side, about 10" long.
This seems about right to me because this is a mass meter, but is that agreed upon by peers or the engineering community?
I have used magnetic flowmeters of Krohne Marshall and Yokogawa makes.
As I remember, they recommend a straight pipe run of about 5D upstream
and 3D downstream of the meter - with pipe size the same as the meter
size.
(Often, for a given flow, you will find that it is more
economical or even necessary to use a flowmeter one size smaller than
the process pipe size, depending on the flow velocity through the
meter).
Within this 5D / 3D distance, no bends, fittings, etc. are allowed.
Further, the angle for reducers / expanders in the vicinity of the flowmeter has to be maximum 4 degree.
I
think, it would be prudent for you to follow the above guideline -
since your line size is only 2", this might not pose any problems.
Actually, volumetric flowmeters that measure fluids which have no
significant effect in density with respect to changes in temperature and
pressure can be considered as massflow meters. If the density gets
effected then you have to have density compensation.
But there
are true massflow meters(for ex. corriolis, thermal etc.) that don't
require density compensation. Straight length requirement is
insignificant in this case.
There is no problem with conductivity
if the water is potable(you will have problems with purified water and
better quality waters apart from other pure liquids). As a thumb rule
you can calculate conductivity as TDS x 0.6.
I
once again caution you to check for full pipe flow as the volumetric
flow calculations consider full pipe diameters. BMSG's suggestion about
the expander and reducers should not be overlooked.
I had an application of using 2 mag meters, I was limited in space so
the configuation was, 10" mag meter, 12" diaphram operated control globe
valve, 12" tee (run-run), 24" of 12" pipe, second 10" mag meter, On
each side of each mag meter was a 12" x 10" reducer, we were not
looking for high accuracy in the second mag meter, just to find out
about how much water was flow in or out of the tee, The first mag meter
was within the accurancy of a turbine meter 2 miles up stream, so it
was OK, the second mag meter read up to 10% low or high (depending upon
the position of the control valve) when it was known there was no
change in flow due to the tee. When the valve was closed and flow from
the tee (bull) to the second mag meter accuracy was better.
Results: 5D is vital when a globe valve is upstream, anything downstream 1d maybe
As
for conductivity, a means of grounding the meter to the water is
required, you can use ground rings installed in the flanges or a
corporation on the downstream side, lack of a good ground will give
fluctating readings at steady flow.
A Mag meter works by inducing
a magnetic field and measuring the deformation of the field by the
fluid moving through the pipe, so small eddies should cancel out hence
the reducers had no effect except to increase velocity for higher
accurancies.
MORE NEWS